WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Table 16: Technical Data ‒ Digital Power Outputs
Response threshold
line break detection
Parallel connection of outputs
Controlling outputs
Response times
Switching
frequency
Capacitive load per output C
Cable length
Test pulse duration
Response threshold
Output monitoring
O1+ ... O4+
Min.
Max.
Resistive load
Inductive load
DC13 acc. to
max.
IEC 60947-5-1
L max.
unshielded
max.
shielded
Min.
Typ.
Max.
66 μA
130 μA
Not possible
See section "Connection Examples"
> ... > "Connecting the Digital Power
Outputs to Digital Inputs"
See section "Technical Data" > ... >
"Response Times"
50 Hz
0.1 Hz (see section "Connect Devices"
> ... > "Switching Inductive Loads")
2.2 µF
200 m
200 m
0 ms ... 500 ms, configurable in steps
(see section "Startup" > ... > "Test
Pulse Duration Parameters")
6 V
9 V
11 V
Version 1.4.2, valid from HW/SW Version 01/02
Device Description
Manual