WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Variant 1: User Acknowledgement via "OA_Req"
9.3.1
For safe PLCs that offer access to the "OA_Req" bit in the PROFIsafe control
byte, the "OA_Req" bit can be used by the safe PLC. The acknowledgement
request from the error is signaled by the PROFIsafe status display element to the
F I/O module. The "OA_Req" bit can be used to reset passivations caused by
PROFIsafe communication errors or other errors. The "F_Ack" bit in the output
process data should not be used for this variant and should be set to 0 by the
safe application. This variant is not supported by all F I/O modules. The figure
below provides a schematic representation of this variant for user
acknowledgement.
Figure 37: Schematic Representation for User Acknowledgement via "OA_Req"
Version 1.4.2, valid from HW/SW Version 01/02
Diagnostics 119
Manual