Appendix; Overview Of Profisafe F Parameters; Table 51: Profisafe F Parameters - WAGO -I/O-SYSTEM 750 Manual

4fdi/4fdo 24v/2a profisafe v2 ipar, fail-safe 4/4 channel digital input/output, 24 vdc, 2 a, profisafe v2.0 ipar
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
12

Appendix

12.1

Overview of PROFIsafe F Parameters

Table 51: PROFIsafe F Parameters

F Parameters
F_Check_SeqNr No Check
F_Check_iPar
F_SIL
F_CRC_Length
Default Value Description
When in PROFIsafe V1 mode, the
F_Check_SeqNr parameter determines
whether the consecutive number of the
PROFIsafe telegrams should be included in
the consistency check (CRC 2 calculation) of
the PROFIsafe telegram.
Because the available safe PLC controllers
only support "No Check", this parameter must
be set accordingly.
When in PROFIsafe V2 mode, the parameter
has no effect.
When in PROFIsafe V1 mode, this parameter
only determines whether the CRC 3 should go
into calculating CRC 1 as the starting value.
CRC 1 is the CRC above the F parameter.
CRC 3 is the CRC above the individual
NoCheck
Parameter.
When in PROFIsafe V2 mode, the meaning of
this parameter changes and has a
manufacturer-specific meaning.
For the F-I/O-Module, this value is always set
to "NoCheck".
The F_SIL parameter specifies the required
safety integrity class of the F-I/O-Module.
SIL3
The F-I/O-Module support SIL3. This value is
specified by the WAGO device description file
(GSD/GSDML).
The F_CRC_Length parameter specifies the
length of the CRC 2 key to be used in the
PROFIsafe telegram.
The required length depends on the length of
the user data to be transferred.
3-byte CRC
Valid combinations are:
F_Par_Version
PROFIsafe V1 mode
PROFIsafe V2 mode
Version 1.4.2, valid from HW/SW Version 01/02
Appendix 135
F_CRC_Length
2-byte CRC
3-byte CRC
Manual