82
Connect Devices
7.3.3.11

Connecting 4 DC Motors

Figure 35: 4 x DC Motor Connection

You can operate a DC motor on each digital power output. Connect the DC motor
between the digital power output Ox+ and Ox−.
If you want to deactivate open load detection for the motors, set the Open load
detection parameter to "not active". Otherwise, set the Open load detection
parameter to "active" so that the F I/O module performs the open load detection
task once per minute.
For more information about configuring the F I/O module, read section
"Commissioning" > ... > "Parameterization of the F I/O modules with the WAGO
Parameterization Tool".
Please note that open load detection may not be part of the safety function under
any circumstances.
You can achieve SIL3/Cat. 4/PL e with this switching.
Open load detection on the digital output
To monitor line interruptions between the digital power outputs Ox+ or Ox- to the
connected DC motor, you can set the Open load detection parameter for each
digital power output separately.
Open load detection is not safety related and cannot be part of the safety
function under any circumstances.
Manual
Version 1.4.2, valid from HW/SW Version 01/02
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar