Commissioning
To load a parameter file saved on the PC for comparison, click the [Open] button
and select whether the data set should appear in the Reference or Comparison
column.
To load the iParameter data from the I/O module currently connected for
comparison, click the [Read] button and select whether the data set should
appear in the Reference or Comparison column.
To return the comparison dialog to its original state, click the [Delete] button.
To print the results of the comparison between to data sets, click the [Print]
button.
To exit the Safety Editor comparison dialog, click the [Close] button.
Changing the password!
Use this function to reset the current password of an I/O module
To change the password, select the Password menu item.
If you have not assigned a password for the selected I/O module, then do so in
the Change PROFIsafe I/O module password dialog.
If you have already assigned a password, then you have to enter the current
password and the new password.
If you do not know the current password, you can use the master password to
assign a new one. The master password is 16 characters long and is
)[4~>#%qM}x=,:$~.
To close the Safety Editor, click on [Exit] in the Safety Editor toolbar.
8.3.2

OFFLINE Mode

When opening the Safety Editor, select whether you want to change a parameter
file already stored on the PC or whether you want to create a new parameter file.
If you want to change a parameter file saved on the PC, you are taken to the
storage location of the last saved parameter file.
If you want to create a new parameter file, you are directed to the storage
location of the default parameter files. From the names of these files, you can
draw conclusions about the type of the supported I/O module and the language
support.
In the Open WAGO Safety Parameter Set dialog, enter the name of the
parameter file that should be loaded. Then click on the [Open] button to load the
selected file.
Manual
Version 1.4.2, valid from HW/SW Version 01/02
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
WAGO-I/O-SYSTEM 750