WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Table 44: Diagnostic Messages
Alarm
Non-supported
F_Block_ID
Non-supported
F_SIL
Safety-oriented
shutdown
Overload
Diagnostic
Module diagnostics
type
Coding
0x004C
LED
Group error (E) red
indication:
PROFIsafe (G) red
The F parameter block signaled by the
F_Block_ID is not supported by the F I/O
Remedy
module. Use an F parameter block
supported by the F I/O module.
Diagnostic
Module diagnostics
type
Coding
0x0044
LED
Group error (E) red
indication:
PROFIsafe (G) red
The F I/O module cannot be operated in
Remedy
the configured SIL. Correct the F
parameterization.
Diagnostic
Module diagnostics
type
Coding
0x0219
LED
Group error (E) red, 2 Hz flashing
indication:
The F I/O module has taken the safe state
and switched off the outputs. Immediately
Remedy
replace the F I/O module and return it to
WAGO Kontakttechnik GmbH & Co. KG
for fault analysis.
Diagnostic
Channel diagnostics
type
Coding
0x0204
LED
Status On (I, K, L or M) red,
indication:
group error (E) red
The maximum permissible load current on
the output of the F I/O module has been
Remedy
exceeded or the + and - connections have
been short circuited. Check the load and
the output wiring.
Version 1.4.2, valid from HW/SW Version 01/02
Diagnostics 115
Description
Manual