750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
If you have assigned a password for the I/O module, you will now be asked to
enter it. After entering the password, the parameter values are transmitted and
verified by the I/O module.
The verified parameter values are then read out of the I/O module and displayed
in the Verification column of the parameter table.
Now compare the parameter values of the "Input" column with the values of the
"Verification" column line by line. If the values are identical, mark the line as
verified by activating the checkbox on the right side next to the Verification
column.
As soon as all lines have been verified (all checkboxes are activated), the
checkbox in the headline of the column is activated automatically.
Now save the new parameter values permanently in the I/O module by clicking
the [Save] button on the Safety Editor toolbar.
The I/O module now permanently stores the parameter values in the F I/O
module. The values are then read out once again and displayed in the Input
column of the parameter table for another check.
If all settings are correct, save the parameter set in a parameter file. To do so,
click [Save] in the Safety Editor toolbar.
The iParameter set description dialog opens for the detailed description of the
parameter file. In this dialog, enter information about the project, the changes
made, and the person responsible. Confirm your entries by clicking [OK].
Then the Save WAGO safety parameter set dialog opens. Enter a name for the
parameter file and select the directory in which the file is to be saved. Then click
on [Save] in order save the file to the hard disk.
To print the parameter values and information on the parameter file, click on the
[Print] button in the Safety Editor toolbar.
The Safety Editor provides additional services. Click the [Services] button on the
System Editor toolbar. A selection menu appears with the Compare and
Password menu items.
Comparison of parameter data!
With this function, only parameter data of the same I/O module type and
iParameter set format can be compared.
To compare two iParameter sets with each other, select the Compare menu
item. The Comparison of iParameter sets dialog opens.
Version 1.4.2, valid from HW/SW Version 01/02