Device Description
4.6.10.5
Response Time of the Digital Power Outputs for a Load between Ox+
and 0 V in the Event of Failure
For the safety response time, take into account the execution times of the
local bus, fieldbus and cycle time of the safe PLC!
To prevent personal and property damage, take into account the execution times
of the local bus, fieldbus and cycle time of the safe PLC in calculating the safety
response time.

Figure 16: Load Bbtween Ox+ and 0 V

The safe response times for the protective wiring depicted above in the figure are
represented in the following table:
Table 28: Response Time of the Digital Power Outputs for a Load between Ox+ and 0 V in the Event
of Failure
Manual
Version 1.4.2, valid from HW/SW Version 01/02
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Test pulse length
0 ms
1 ms
2 ms
5 ms
10 ms
20 ms
50 ms
100 ms
200 ms
500 ms
WAGO-I/O-SYSTEM 750
Safe response time
46 ms
46 ms
46 ms
46 ms
46 ms
46 ms
66 ms
116 ms
216 ms
516 ms