Powerlink Option Related Drive Parameters - YASKAWA SI-EL3/V Installation Manual

V1000 series option ethernet powerlink
Hide thumbs Also See for SI-EL3/V:
Table of Contents

Advertisement

6 Powerlink Option Related Drive Parameters

6
Powerlink Option Related Drive Parameters
The drive parameters listed in
option card. Check these parameters before starting network communications.
No.
Name
Frequency
b1-01
Reference
<1>
Selection
b1-02
Run Command
<1>
Selection
E2-04
Motor 1 Motor
<2>
Poles
Operation
Selection after
F6-01
Communications
Error
External Fault
F6-02
Detection
Conditions (EF0)
Stopping Method
for External Fault
F6-03
from
Communication
Option Board
Torque Reference/
Torque Limit
F6-06
selection from
<4>
Communications
Option
NetRef/ComRef
F6-07
Selection Function
EN 20
Table E.6
have influence on some functions of the SI-EL3/V
Table E.6 Parameter Settings
Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminals
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse Input (Terminal RP)
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option card
Set the number of motor poles described on the motor nameplate.
2 to 48
Determines drive response when a bUS error is detected during
communications with the Powerlink Option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
<3>
Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation
Determines drive response for external fault input (EF0) detection during
Powerlink communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
<3>
0: Torque reference/torque limit via network communications are
disabled.
1:
Torque reference/torque limit via network communications are
enabled.
<5>
0: Multi-step speed reference disabled (F7 mode)
1: Multi-step speed reference allowed (V7 mode)
YASKAWA Europe YEU TOEP C710606 87A - V1000 Option Powerlink - Installation Manual
Description
Default
<6>
1
4
1
0
1
0
0