Drive-Cliq Interface X400-X402; Meaning Of The Leds On The Power Module - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

5.3.2.7

DRIVE-CLiQ interface X400-X402

Table 5- 49
DRIVE-CLiQ interface X400-X402
Pin
1
2
3
4
5
6
7
8
A
B
5.3.2.8

Meaning of the LEDs on the Power Module

Table 5- 50
Meaning of the LEDs "READY" and "DC LINK" on the Control Interface Module on the Power Module
LED state
READY
Off
Off
Off
Orange
Green
Red
Orange
Orange
Red
---
Green/Red
–--
(0.5 Hz)
Green/Red
---
(2 Hz)
Green/orange
---
or
red/orange
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
Name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
DC LINK
The electronics power supply is missing or outside the permissible tolerance
range.
The component is ready for operation and cyclic DRIVE-CLiQ communication is
taking place.
The component is ready for operation and cyclic DRIVE-CLiQ communication is
taking place. The DC-link voltage is present.
The component is ready for operation and cyclic DRIVE-CLiQ communication is
taking place. The DC-link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
The LED is activated irrespective of whether the corresponding messages have
been reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Recognition of the component via LED is activated (see SINAMICS S120/S150
List Manual.)
Remark:
Both options depend on the LED status when component recognition is activated
using the parameter.
5.3 Power Modules Chassis
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronics ground
Description
Power Modules