Cabinet design and EMC for components, Blocksize format
11.7 Protective connection and equipotential bonding
Figure 11-5
386
Within a machine/system, ensure that the protective conductor for the line feeder cable fulfills
at least one of the following conditions:
For fixed connection:
The protective conductor is routed so that along its complete length it is protected against
mechanical damage.
1)
As a conductor of a multi-conductor cable, the protective conductor has a cross-section ≥
2.5 mm
Cu.
2
For an individual conductor, the protective conductor has a cross-section ≥ 10 mm²
The protective conductor consists of two conductors with the same cross-section.
When establishing the connection using an industrial plug connector according to EN 60309:
As a conductor of a multi-conductor cable, the protective conductor has a cross-section ≥
2.5 mm
Cu.
2
Cables routed within control cabinets or closed machine housings are considered to be
1)
adequately protected against mechanical damage.
The cable cross-sections must be dimensioned in compliance with local installation rules for
the rated current of the Power Module.
Minimum cross section 6 mm
6 mm
can this connection be appropriately reduced.
2
Same cross-section as the line conductor.
Protection connection concept for Power Modules blocksize format
Cu. Only if the cross-section of the conductors is
2
less than
Manual, 06/2019, 6SL3097-5AL00-0BP1
Cu.
2
AC Drive