Siemens SINAMICS S120 Equipment Manual page 275

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

LED
Color
COM
-
Green
Red
MOD
-
OUT > 5 V
-
Orange
Make sure that the encoder connected is designed for a 24 V supply. Connecting a 5 V encoder to a 24 V supply can
1)
result in destruction of the encoder electronics.
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
State
Description / cause
OFF
Cyclic communication is not (yet) running.
Note:
The PROFIdrive is ready for communication when
the Control Unit is ready for operation (see LED:
RDY).
Continuous light
Cyclic communication is taking place.
Flashing light
Cyclic communication is not yet fully up and
0.5 Hz
running.
Possible causes:
- the controller is not transmitting any setpoints.
- in the isochronous mode, the controller is not
sending a GC (Global Control) or it is sending a
defective GC
Flashing light
The PROFIBUS master is sending a faulty
0.5 Hz
parameter assignment or the configuration file is
corrupted.
Flashing light
Cyclic bus communication has been interrupted or
2 Hz
could not be established.
OFF
-
OFF
-
Continuous light
The voltage of the electronics power supply for the
measuring system is 24 V.
Control Units, Control Unit Adapters and operating components
8.4 Control Unit CU310-2 DP (PROFIBUS)
1)
Remedy
-
-
-
Modify the
configuration between
master/controller and
control unit.
Rectify the fault in bus
communication.
-
-
273