3.5 System data
Rated pulse frequency
For devices with 1/3 AC 200 V rated voltage
For devices with 3 AC 400 V rated voltage
and a type rating ≤ 90 kW based on I
and a type rating ≥ 110 kW based on I
For devices with 3 AC 690 V line voltage
Output voltage
Output frequency
When using a motor holding brake, possibly restricted voltage tolerances (24 V ±10 %) must be taken into account.
1)
Higher output frequencies available on request. In this case, an additional license is required.
2)
Table 3- 2
Degree of protection / protection class
Degree of protection
Protection class, line supply circuits
Electronic circuits
Cooling method
Internal air cooling
External air cooling
Table 3- 3
Environmental conditions
Chemically active substances
Long-term storage
Transport
Operation
Biological environmental conditions
Long-term storage
Transport
Operation
Climatic environmental conditions
Long-term storage
Transport
Operation
40
4 kHz
4 kHz
n
2 kHz
n
2 kHz
Approx. 0.95 • line voltage (maximum value)
approx. 0.74 • line voltage at 1 AC 200 V
0 ... 550 Hz, dependencies on the control mode and pulse
frequency must be taken into account
IP20 acc. to IEC 60529, open type acc. to UL/CSA
I, with protective conductor connection
extra-low-voltage PELV/SELV
Forced air cooling AF acc. to EN 60146
Push Through cooling type
Class 1C2 according to EN 60721-3-1, in product packaging
Class 2C2 according to EN 60721-3-2, in transport packaging
Class 3C2 according to EN 60721-3-3 (for the drive system)
Class 3C3 according to EN 60721-3-3 (for the Power Modules)
Class 1B1 according to EN 60721-3-1, in product packaging
Class 2B1 according to EN 60721-3-2, in transport packaging
Class 3B1 according to EN 60721-3-3
Class 1K4 according to EN 60721-3-1, in product packaging
Temperature: -25 ... +55 °C
Relative humidity: 5 ... 95 %
Class 2K4 according to EN 60721-3-2, in transport packaging
Temperature: -40 ... +70 °C
Relative humidity: 5 ... 95 %
Class 3K3 according to EN 60721-3-3
2)
1)
2)
1)
2)
1)
2)
3)
Manual, 06/2019, 6SL3097-5AL00-0BP1