Connecting The Dv/Dt Filter Compact Plus Voltage Peak Limiter - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor-side power components
7.2 Chassis
7.2.4.4

Connecting the dv/dt filter compact plus Voltage Peak Limiter

Figure 7-17
Connecting the dV/dt filter compact plus Voltage Peak Limiter
Cable cross-sections
Table 7- 19
dV/dt filter compact plus Voltage
Peak Limiter
6SL3000-2DE32-6EA0
6SL3000-2DE35-0EA0
Fire due to ground fault / short-circuit
Inadequate installation of the cables to the Motor Module DC link can result in a ground
fault/short-circuit and place persons at risk as a result of the associated smoke and fire.
• Apply the local installation regulations to avoid this fault.
• Protect the cables against mechanical damage.
• Also implement one of the following measures:
NOTICE
Damage to the du/dt filter compact due to mechanical load on connections
The connections on the dv/dt filter compact have not been designed for the direct
mechanical connection of the motor cables.
• Take measures on the installation to ensure that the connections cannot be deformed
218
Cable cross-sections for connections between a dV/dt filter and Power Module
WARNING
– Use cables with double insulation.
– Maintain adequate clearance, e.g. by using spacers.
– Lay the cables in separate cable ducts or conduits.
by the mechanical load exerted by the connected cables.
Cross-section
Connection on dV/dt filter
[mm²]
16 (AWG 6)
Screw M8 / 12 Nm (106 lbf in)
25 (AWG 4)
Screw M8 / 12 Nm (106 lbf in)
Manual, 06/2019, 6SL3097-5AL00-0BP1