Ambient temperature
4)
Relative humidity
Degree of pollution
Installation altitude
Operation
Mechanical environmental conditions
Long-term storage
Transport
Operation
Vibration test in operation
Shock test in operation
Product packaging (storage packaging) is individual packaging for storage - and does not satisfy the requirements for
1)
transport. As a consequence, product packaging is therefore not suitable for shipping.
Transport packaging is either packaging that is directly suitable for transport, or secondary packaging which, together
2)
with the product packaging, satisfies the requirements for transport.
Increased ruggedness regarding temperature range and relative humidity; therefore better than 3K3
3)
Permissible ambient temperatures for Control Units and Control Unit Adapter, see the relevant technical data
4)
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
FSA to FSC
Without derating
-10 ... +40 °C for operation with low overload
-10 ... +50 °C for operation with high overload
(S6 load cycles only to +40 °C)
With derating
-10 ... +60 °C
FSD to FSG
Without derating
-20 ... +40 °C for operation with low overload
-20 ... +50 °C for operation with high overload
(S6 load cycles only to +40 °C)
With derating
-20 ... +60 °C
5 ... 95 % no condensation
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water,
splashing water and water jets are not permitted
2 according to EN 61800-5-1
0 ... 1000 m above sea level without derating
> 1000 ... 4000 m
Reduction of the output current by 10 % per 1000 meters, or
•
Reduction in the ambient temperature by 5 °C per 1000 meters
•
> 2000 ... 4000 m above sea level
Operation on line supply systems with grounded neutral point, or
•
Operation on an isolating transformer with secondary grounded neutral point
•
Class 1M2 according to EN 60721-3-1, in product packaging
Class 2M3 according to EN 60721-3-2, in transport packaging
Class 3M1 according to EN 60721-3-3
According to IEC 60068-2-6 test Fc (sinusoidal)
10 ... 57 Hz: 0.075 mm deflection amplitude
•
57 ... 150 Hz: 1g acceleration amplitude
•
10 frequency cycles per axis
•
According to IEC 60068-2-27 test Ea (half-sine)
5 g peak acceleration
•
30 ms duration
•
3 shocks in all three axes in both directions
•
System overview
3.5 System data