An opening above the connections for the braking resistor (R1, R2) is provided in the cover
for connecting the cable to the braking resistor.
Note
You must carefully observe the specified tightening torques.
6.2.1.11

Technical data

Table 6- 12
Technical data, Braking Modules
Article number
Suitable for installation in Power Modules, frame size
P
power (unit rating)
DB
P
power (peak power)
15
P
power
20
P
power
40
Variable response thresholds
Digital input
Rated voltage
Low signal level
(an open digital input is interpreted as "low")
High level
Current drain 
 ( typical at 24 VDC)
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
Remove the three screws on the blanking cover.
Remove the blanking cover.
Install the Braking Module instead of the blanking cover and
secure it with the blanking cover screws that were
previously removed.
Secure the connecting cable to the DC link with two screws
(Braking Module connection) and with two nuts (DC-link
connection).
Attach the
- cover plate, top – step
- cover plate, left – step
- the front cover – step
6SL3300–1AE31-3AA0
FX
25 kW
125 kW
100 kW
50 kW
774 V (673 V)
-3 ... 30 V
-3 ... 5 V
15 ... 30 V
10 mA
DC link components
6.2 Chassis
6SL3300–1AE32-5AA0
GX
50 kW
250 kW
200 kW
100 kW
774 V (673 V)
-3 ... 30 V
-3 ... 5 V
15 ... 30 V
10 mA