Siemens SINAMICS S120 Equipment Manual page 119

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 5- 24
Technical data of the PM240-2, FSB (200 V)
Line voltage 1 AC / 3 AC 200 ... 240 V ±10 %
Article No.
without integrated line filter
with integrated line filter
Output current
Rated current I
1)
n
Base load current I
H
for S6 duty (40 %) l
S6
Peak current l
max
Type rating
2)
based on I
/ based on I
n
H
Rated pulse frequency
Max. pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1 m)
24 V DC supply
for the Control Unit
Rated input current 1 AC / 3 AC
Resistance value of the external
braking resistor
Max. cable length
to braking resistor
Line connection L1, L2,
Motor connection U2, V2, W2,
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
Max. motor cable length
shielded/unshielded
Degree of protection
Weight
without / with line filter
Rated current I
covers the load cycle for Low Overload.
1)
n
Rated power of a typical standard induction motor at 230 V.
2)
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
3)
(based on I
) for a line impedance corresponding to u
rated
To observe the limit values of EN 61800-3 Category C2, for Power Modules PM240-2 with integrated line filter 50 m
4)
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power
Module with an external line filter for Category C2 and a motor reactor.
Power loss in the control cabinet: 0.045 kW. The remaining power loss is dissipated through the heat sink.
5)
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
6SL3210–
1PB15-5UL0
1PB15-5AL0
A
5.5
A
3.9
A
6.1
A
8.3
kW
1.1 / 0.75
kHz
4
kHz
16
kW
0.05
l/s
9.2
dB
61.5
A
1.0
A
13.5 / 7.8
3)
Ω
≥ 68
m
15
Screw-type terminals
Cross head M2.5
Conductor cross section: 1.5 ... 6 mm
Tightening torque: 0.6 Nm (5.3 lbf in)
4)
m
50 / 100
IP20
kg
2.9 / 3.1
5.2 Blocksize Power Modules (PM240-2)
Internal
6SL3210–
1PB17-4UL0
1PB17-4AL0
7.4
5.5
8.2
11.1
1.5 / 1.1
4
16
0.07
9.2
61.5
1.0
18.1 / 9.7
≥ 68
15
(AWG 16 ...10)
2
2.9 / 3.1
= 1 %.
k
Power Modules
Push-through
6SL3210–
6SL3211–
1PB21-0UL0
1PB21-0UL0
1PB21-0AL0
1PB21-0AL0
10.4
10.4
7.4
7.4
11.5
11.5
15.6
15.6
2.2 / 1.5
2.2 / 1.5
4
4
16
16
0.12
0.12
5)
9.2
9.2
61.5
61.5
1.0
1.0
24.0 / 13.6
24.0 / 13.6
≥ 68
≥ 68
15
15
in the cabinet:
IP20
outside: IP54
2.9 / 3.1
3.4 / 3.7
117