Cabinet design and EMC for components, Blocksize format
11.5 24 V DC Supply Voltage
11.5.5

Selecting power supply units

You are advised to use the devices in the following table. These devices meet the applicable
requirements of EN 60204-1.
Table 11- 4
Recommended SITOP Power
Rated output
Phases
current [A]
5
1 / 2
10
1 / 2
20
1 / 2
3
40
1 / 2
3
Hazardous voltage when connecting an unsuitable power supply
If a power supply is connected that is not suitable, parts and components of the device
could be live (under voltage). Touching live components can result in death or severe
injury.
• Connect the ground potential to the PE conductor connection.
• Mount the power supply close to the drive lineup.
376
Rated input voltage [V]
Operating voltage range [V]
AC 120 ... 230/230 ... 500
85 ... 264/176 ... 550
AC 120 ... 230/230 ... 500
85 ... 264/176 ... 550
AC 120 / 230
85 ... 132/176 ... 264
3 AC 230/400 ... 288/500
320 ... 550
AC 120/230
85 ... 132/176 ... 264
3 AC 230/400 ... 288/500
320 ... 550
WARNING
Ideally, they should be mounted on a common mounting plate. If different mounting
plates are used, they must be electrically connected in compliance with the
Configuration Manual, "EMC installation guideline".
Short-circuit current [A]
Approx. 5.5 (powering up)
Typ. 15 for 25 ms (in
operation)
Approx. 12 (powering up)
Typ. 30 for 25 ms (in
operation)
Approx. 23 (powering up)
Typ. 60 for 25 ms (in
operation)
Approx. 46 (powering up)
Typ. 120 for 25 ms (in
operation)
Manual, 06/2019, 6SL3097-5AL00-0BP1
Article No.
6EP1333-3BA00-8AC0
6EP1334-3BA00-8AB0
6EP1336-3BA00-8AA0
6EP1436-3BA00-8AA0
6EP1337-3BA00-8AA0
6EP1437-3BA00-8AA0