Power Modules - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Power Modules

5.2 Blocksize Power Modules (PM240-2)
5.2.8.1
200 V Power Modules
Table 5- 23
Technical data of the PM240-2, FSA (200 V)
Line voltage 1 AC / 3 AC 200 ... 240 V ±10 %
Article No.
without integrated line filter
with integrated line filter
Output current
Rated current I
n 1)
Base load current I
H
for S6 duty (40 %) l
S6
Peak current l
max
Type rating
2)
based on I
/ based on I
n
H
Rated pulse frequency
Max. pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1 m)
24 V DC supply
for the Control Unit
Rated input current 1 AC / 3 AC
Resistance value of the external
braking resistor
Max. cable length
to braking resistor
Line connection L1, L2,
Motor connection U2, V2, W2,
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
Max. motor cable length
4)
shielded/unshielded
Degree of protection
Weight
without / with line filter
Rated current I
covers the load cycle for Low Overload.
1)
n
Rated power of a typical standard induction motor at 230 V.
2)
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
3)
(based on I
) for a line impedance corresponding to u
rated
To observe the limit values of EN 61800-3 Category C2, for Power Modules PM240-2 with integrated line filter 50 m
4)
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power
Module with an external line filter for Category C2 and a motor reactor.
Power loss in the control cabinet: 0.02 kW. The remaining power loss is dissipated through the heat sink.
5)
116
6SL3210–
1PB13-0UL0
1PB13-0AL0
A
3.0
A
2.3
A
3.3
A
4.6
kW
0.55 / 0.37
kHz
4
kHz
16
kW
0.04
l/s
5
dB
49.2
A
1.0
A
7.5 / 4.2
3)
Ω
≥ 200
m
15
Screw-type terminals
Cross head M2.5
Conductor cross section: 1.5 ... 2.5 mm
Tightening torque: 0.5 Nm (4.4 lbf in)
m
50 / 100
IP20
kg
1.4 / 1.6
Internal
6SL3210–
1PB13-8UL0
1PB13-8AL0
3.9
3.0
4.3
6.0
0.75 / 0.55
4
16
0.04
5
49.2
1.0
9.6 / 5.5
≥ 200
15
2
1.4 / 1.6
= 1 %.
k
Push-through
6SL3211–
1PB13-8UL0
1PB13-8AL0
3.9
3.0
4.3
6.0
0.75 / 0.55
4
16
0.04
5)
5
49.2
1.0
9.6 / 5.5
≥ 200
15
(AWG 16 ... 14)
in the cabinet: IP20
outside: IP54
1.8 / 2.0
Manual, 06/2019, 6SL3097-5AL00-0BP1
AC Drive

Advertisement

Table of Contents
loading