Siemens SINAMICS S120 Equipment Manual page 45

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 3- 7
Environmental conditions
Chemically active substances
Long-term storage
1)
Transport
1)
Operation
Biological environmental conditions
Long-term storage
1)
Transport
1)
Operation
Climatic environmental conditions
Long-term storage
1)
Transport
1)
Operation
Mechanical environmental conditions
Long-term storage
Transport
1)
Operation
Vibration test in operation
Shock test in operation
Installation altitude
Operation
In transport packaging
1)
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
Class 1C2 according to EN 60721-3-1
Class 2C2 according to EN 60721-3-2
Class 3C2 according to EN 60721-3-3
Class 1B1 according to EN 60721-3-1
Class 2B1 according to EN 60721-3-2
Class 3B1 according to EN 60721-3-3
Class 1K4 according to EN 60721-3-1
Temperature: -25 ... +55 °C
Class 2K4 acc. to EN 60721-3-2
Temperature: -25 ... +70 °C
max. Air humidity: 95% at +40°C
Class 3K3 according to EN 60721-3-3
Temperature: 0 ... +40 °C without derating
> 40 ... +55 °C with reduction of the output current by 2.67 % pro °C
Relative humidity: 5 ... 90 % no condensation
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water,
splashing water and water jets are not permitted
-
Class 2M2 according to EN 60721-3-2
According to IEC 60068-2-6 test Fc (sinusoidal)
10 ... 57 Hz: 0.075 mm deflection amplitude
57 ... 150 Hz: 1g acceleration amplitude
According to IEC 60068-2-27 test Ea (half-sine)
10 g peak acceleration
20 ms duration
0 ... 2000 m above sea level without derating
> 2000 ... 4000 m
Reduction of the output current by 10 % per 1000 meters, or
Reduction of the ambient temperature by 5°C per 1000 meters
Operation on line supply systems with grounded neutral point, or
Operation on an isolating transformer with secondary grounded neutral point
System overview
3.5 System data
43