DC link components
6.2 Chassis
6.2.1.2
Safety instructions for Braking Modules chassis format
Electric shock due to the residual charge of the DC link capacitors
Because of the DC link capacitors, a hazardous voltage is present for up to five minutes
after the power supply has been switched off. Contact with live parts can result in death or
serious injury.
• Only carry out work on these components after this time has elapsed.
• Measure the voltage before starting work on the DCP and DCN DC-link terminals.
Fire and device damage as a result of ground fault/short-circuit
The cables to the braking resistor must be routed so that a ground fault or short circuit can
be ruled out. A ground fault can result in fire with associated smoke.
• Comply with local installation regulations, which allow this fault to be ruled out.
• Protect the cables from mechanical damage.
• In addition, apply one of the following measures:
NOTICE
Damage to braking resistors that are not permissible
An impermissible braking resistor may become damaged.
• Only use braking resistors that SIEMENS has authorized for SINAMICS.
172
WARNING
WARNING
– Use cables with double insulation.
– Observe adequate clearances, e.g. through the use of spacers.
– Route the cables in separate cable ducts or pipes.
Manual, 06/2019, 6SL3097-5AL00-0BP1
AC Drive