8.4 Control Unit CU310-2 DP (PROFIBUS)
Terminal
DI: Digital input; DI/DO: Bidirectional digital input/output
1)
The rapid inputs can be used as probe inputs or as inputs for the external zero mark
2)
Data for: V
= 24 V; load 48 Ω; high ("1") = 90% V
3)
cc
The maximum cable length that can be connected is 30 m.
Note
An open input is interpreted as "low".
Terminal M2 must be connected so that the digital inputs (DI0 ... DI3) can be used. This is
achieved through one of the following measures:
• Provide the ground reference of the digital inputs.
• A jumper to terminal M (this removes the electrical isolation for these digital inputs).
Note
A 24 V supply voltage must be connected to terminal X124 for the digital outputs to be used.
If momentary interruptions in the voltage occur in the 24 V supply, the digital outputs are
deactivated until the interruption has been rectified.
8.4.2.9

X124 Electronics power supply

Table 8- 31
X124 Electronics power supply
Terminal
+
+
M
M
Type: Screw-type terminal 2 (Page 384)
Max. cross-section that can be connected: 2.5 mm
The screw terminal must be tightly screwed using a flat-bladed screwdriver.
The maximum cable length that can be connected is 30 m.
If the 24 V supply is not connected, the digital outputs of the following interfaces cannot be
used:
● X121 (DO8 to DO11)
● X131 (DO12 to DO15)
262
Designation
Technical data
1)
; low ("0") = 10% V
out
Designation
Electronics power supply
Electronics power supply
Electronics ground
Electronics ground
(AWG 14)
2
out
Technical data
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: Max. 1.0 A (without DRIVE-CLiQ or
digital outputs)
Max. current via jumper in connector: 20 A (15 A
according to UL/CSA)