Siemens SINAMICS S120 Equipment Manual page 126

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Power Modules
5.2 Blocksize Power Modules (PM240-2)
Table 5- 31
Technical data of the PM240-2, FSA (400 V) (2/2)
Line voltage 3-phase 380 ... 480 V AC ± 10%
Article No.
without integrated line filter
with integrated line filter
Output current
Rated current I
1)
n
Base load current I
H
for S6 duty (40 %) l
S6
Peak current l
max
Type rating
2)
based on I
/ based on I
n
H
Rated pulse frequency
Max. pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1 m)
24 V DC supply
for the Control Unit
Rated input current
3)
Resistance value of the external
braking resistor
Max. cable length
to braking resistor
Line connection L1, L2, L3,
Motor connection U2, V2, W2,
DC-link connection, connection for
braking resistor
DCP/R1, DCN, R2
Max. motor cable length
4)
shielded/unshielded
Degree of protection
Weight
without / with line filter
Rated current I
covers the load cycle for Low Overload.
1)
n
Rated power of a typical standard induction motor at 400 V 3 AC
2)
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
3)
(based on I
) for a line impedance corresponding to u
rated
To observe the limit values of EN 61800-3 Category C2, for Power Modules PM240-2 with integrated line filter 50 m
4)
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power
Module with an external line filter for Category C2 and a motor reactor.
Power loss in the control cabinet: 0.02 kW. The remaining power loss is dissipated through the heat sink.
5)
124
6SL3210–
1PE16-1UL1
1PE16-1AL1
A
5.9
A
4.1
A
6.5
A
8.9
kW
2.2 / 1.5
kHz
4
kHz
16
kW
0.1
l/s
5
dB
56.3
A
1.0
A
7.7
Ω
≥ 140
m
15
Screw-type terminals
Cross head M2.5
Conductor cross section: 1.5 ... 2.5 mm
Tightening torque: 0.5 Nm (4.4 lbf in)
m
50 / 100
IP20
kg
1.4 / 1.5
= 1 %.
k
Internal
6SL3210–
1PE18-0UL1
1PE18-0AL1
7.7
5.9
8.5
11.8
3.0 / 2.2
4
16
0.12
5
56.3
1.0
10.1
≥ 140
15
(AWG 16 ... 14)
2
1.4 / 1.5
Manual, 06/2019, 6SL3097-5AL00-0BP1
Push-through
6SL3211–
1PE18-0UL1
1PE18-0AL1
7.7
5.9
8.5
11.8
3.0 / 2.2
4
16
0.12
5)
7
56.3
1.0
10.1
≥ 140
15
in the cabinet: IP20
outside: IP54
1.7 / 1.8
AC Drive

Advertisement

Table of Contents
loading

Table of Contents