X130 Digital Input (Fail Safe) Digital Output - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Control Units, Control Unit Adapters and operating components
8.3 Control Unit CU310-2 PN (PROFINET)
8.3.2.9

X130 digital input (fail safe) digital output

Table 8- 11
X130 Digital Input / Failsafe Digital Output
Terminal
1
2
3
4
5
6
7
8
Type: Spring-loaded terminal 1 (Page 384)
Max. cross-section that can be connected: 1.5 mm
DI: Digital input/DO: Digital output
1)
F-DO: Fail-safe digital output
2)
The maximum cable length that can be connected is 30 m.
Fail-safe digital output
The F-DO consists of a high-side switch and a low-side switch.
For applications without the safety function, the high-side switch may be used as an
additional digital output. The low side switch is not available.
Note
If the 24 V supply is briefly interrupted, the digital output is deactivated until the interruption
has been rectified.
240
Designation
Technical data
1)
DI 22+
Voltage: -3 ... +30 V DC
Electrical isolation: Yes
DI 22-
Reference potential: M2
Input characteristic acc. to IEC 61131-2, type 1
Input voltage (including ripple)
"1" signal: 15 ... 30 V
"0" signal: -3 ... +5 V (at ≤ 2 mA)
Input current
at 24 V DC: typ. 3.5 mA
For "1" signal: > 0.5 mA
Input delay (typ.):
For "0" → "1": 50 μs
For "1" → "0": 150 μs
protected against polarity reversal
M2
Reference potential for digital inputs DI 0 to DI 3
GND
Ground reference for the electronics
M1
Reference potential for DI 16, DI 18, DI 20 and DO 16
24 V1
Power supply for DO 16
DO 16+
F-DO 0
Voltage: 24 V DC
2)
Max. Load current per output: 500 mA
DO 16-
Output delay (typ./max.):
For "0" → "1": 150 µs / 400 μs
For "1" → "0": 75 µs / 100 μs
Short-circuit, ground fault, overload proof
Automatic switch on again after overload trip
(AWG 16)