Power Modules
4.3 Power Modules Chassis
Fire hazard due to overheating when permissible connection cable lengths are exceeded
Excessively long connection cables on terminal strip X46 can cause components to
overheat with the associated risk of fire and smoke.
• A maximum cable length of 10 m must not be exceeded.
• The cable must not be brought outside the control cabinet or control cabinet group.
4.3.2.7

DRIVE-CLiQ interface X400-X402

Table 4- 44
DRIVE-CLiQ interface X400-X402
Pin
1
2
3
4
5
6
7
8
A
B
146
WARNING
Name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
GND (0 V)
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronic ground
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5