Note
Protective conductor connection
The protective conductor connection for the braking resistor is established via the shield
connection for frame sizes FSA to FSC.
For installation according to EN 60204-1 and EN 61800-5-1, the protective conductor
connection at the housing must be used. The protective cable conductor in the pigtail is, in
this case, not to be used, but can be suitably tied off or cut off.
For frame sizes FSD to FSF, the protective conductor connection of the braking resistor is
connected at the sheet steel enclosure above terminals R1 and R2. Optionally, additional
shield connecting plates can be ordered from Siemens.
6.1.1.6

Technical data

Line voltage 1/3 AC 200 V to 240 V ±10 %
Note
Additional combinations are possible through our "Siemens Product Partners for Drive
Options
zubehoer/Seiten/sinamics-zubehoer.aspx)".
Note
Braking resistors FSD ... FSF
Only use braking resistors that are UL approved, and have successfully passed the
"Abnormal Operation Test" according to UL 508.
Table 6- 3
Braking resistors for Blocksize PM240-2, 200 V, FSA - FSC
Manufacturer
Article number JJY:023...
Resistance
Type rating P
DB
Peak power P
max
Load duration for peak power T
Period duration of braking duty
cycle T
Degree of protection
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
(https://w3.siemens.com/mcms/mc-drives/de/niederspannungsumrichter/sinamics-
146720008
Ω
200
kW
0.0375
kW
0.75
s
12
a
s
240
IP20
Heine Resistors GmbH
151720007
163720018
68
37
0.11
0.20
2.2
4.0
12
12
240
240
IP20
IP20
DC link components
6.1 Blocksize
433720001
20
0.375
7.5
12
240
IP20
165