Ac Supply 400V / 3-Phase; Line Terminal Strip X1A; Figure 8: Connection Of The Mains Supply 400 Vac / 3-Phase; Figure 9: Line Terminal Strip X1A - KEB COMBIVERT G6M Instructions For Use Manual

Motor inverter
Table of Contents

Advertisement

4.2.2 Ac supply 400V / 3-phase

L1
L2
L3
PE
No.
Type
Mains voltage
Mains form
1
Personal protection
(if required)
2
Main fuses
3
Mains contactor
4
Mains choke (optional)
5
Figure 8:
Connection of the mains supply 400 VAC / 3-phase

4.2.3 Line terminal strip X1A

X1A
Figure 9:
Line terminal strip X1A
34
TN, TT
RCMA with separator or RCD
type B
Type gG or MCCB
-
07Z1B02-1000, 09Z1B02-1000 or 10Z1B04-1000
KEB COMBIVERT
Name
function
Mains connection
L1, N
1-phase
Mains connection
L1, L2, L3
3-phase
Connection for protec-
PE,
tive earth
T1 T2
L1
U
L2
V
L3
W
PE
PE
Description
3-phase 400 V AC
Earth leakage monitor
cross-section
0.2...2.5 mm²
AWG 24...12
0.2...2.5 mm²
AWG 24...12
Screw M4
IT
-
Tightening
torque
0.5...0.6 A
5...7 lb-inch
0.5...0.6 A
5...7 lb-inch
1.3 Nm
11 lb-inch