6.3.3
Specifying the setpoint via the fieldbus
Interconnecting the fieldbus with the main setpoint
Figure 6-18
Most standard telegrams receive the speed setpoint as a second process data PZD2.
Table 6- 18
Parameter
p1070 = 2050[1]
p1075 = 2050[1]
6.3.4
Electromechanical potentiometer
The converter has an electromechanical potentiometer.
The potentiometer is hardwired with the internal analog input 2.
When using USS or Modbus communications, the potentiometer provides
by default the main setpoint.
Figure 6-19
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Fieldbus as setpoint source
Setting the fieldbus as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with process data PZD2 from the fieldbus.
Additional setpoint
Interconnect the additional setpoint with process data PZD2 from the fieldbus.
Potentiometer as setpoint source
Advanced commissioning
6.3 Setpoints