Parameter
p20033 = 440
p20159 = 5000.00
p20158 = 722.0
p20030[0] = 20160
p20030[1] = 722.1
p0840 = 20031
Explanation of the example using the ON/OFF1 command
Parameter p0840[0] is the input of the "ON/OFF1" block of the inverter. Parameter r20031 is
the output of the AND block. To interconnect ON/OFF1 with the output of the AND block, set
p0840 = 20031.
Figure A-6
Note
For the basic commissioning, you determine the function of the interfaces for your converter
via predefined settings (p0015).
If you subsequently select a different predefined setting for the function of the interfaces,
then all interconnections that you changed will be lost.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Description
Run sequence of the AND logic block within runtime group 5 (processing
after the time block)
Setting the delay time [ms] of the time module: 5 seconds
Connect the status of DI 0 to the input of the time block
r0722.0 = Parameter that displays the status of digital input 0.
Interconnect the timer block to the 1st input of the AND
Interconnect the status of DI 1 with the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
Interconnect the AND output to ON/OFF1
Interconnecting blocks by setting p0840[0] = 20031
A.6 Interconnecting signals in the inverter
Appendix
325