It is not permissible to use speed control in the following cases:
● If the motor is too small in comparison to the converter (the rated motor power must not
be less than one quarter of the rated converter power)
● When you operate several motors on one converter
● When the maximum motor speed exceeds the following values:
Pole number of the motor
Maximum motor speed [rpm]
5.2.4

Defining additional requirements for the application

Minimum and maximum speed
● Minimum speed - factory setting 0 [rpm]
The minimum speed is the lowest speed of the motor independent of the speed setpoint.
A minimum speed is, for example, useful for fans or pumps.
● Maximum speed - factory setting 1500 [rpm]
The inverter limits the motor speed to this value.
Operate the inverter with the factory setting
For basic applications, you can try to operate the drive with a rated power < 18.5 kW without
any other commissioning steps. Check whether the control quality of the drive without
commissioning is adequate for the requirements of the application.
We recommend that you configure the drive with the precise motor data.
5.3

Basic commissioning

5.3.1

Motor data using p300 and p301

Preassigned motor data using p0300 and p0301
The SINAMICS G110M software has been configured to utilize the input of the motor data
using a motor code. There are two parameters associated with this function, they are p0300
(motor type) and p0301 (motor code).
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Converter pulse frequency
5.3 Basic commissioning
2 kHz
4 kHz and higher
4-pole
4980
Commissioning
4-pole
7200
101