Advanced Commissioning - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Advanced commissioning

6.5 Motor control
5. Check whether the motor is following the setpoint.
6. If necessary, increase the voltage boost p1311 until the motor accelerates without
problem.
In applications with a high break loose torque, you must additionally set parameter p1312
higher to achieve a satisfactory response.
You have set the voltage boost.
Parameter
p1310
p1311
p1312
You will find more information on this function in the parameter list and in function diagram
6301 in the List Manual.
182
Description
Starting current (voltage boost) permanent (factory setting 50 %)
Compensates for voltage drops caused by long motor cables and the ohmic losses in
the motor.
Starting current (voltage boost) when accelerating (factory setting 0 %)
Provides additional torque when the motor accelerates.
Starting current (voltage boost) when starting (factory setting 0 %)
Provides additional torque, however, only when the motor accelerates for the first time
after it has been switched on ("break loose torque").
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG

Advertisement

Table of Contents
loading

Table of Contents