Activate and deactivate write protection
Procedure with STARTER
Proceed as follows to activate or deactivate the write protection:
1. Go online.
2. Open the inverter shortcut menu.
3. Activate or deactivate write
protection.
4. Press the "Copy RAM to ROM"
button to retentively save the
settings
You have activated or deactivated write protection.
Parameters
r7760
p7761
Exceptions to write protection
Some functions are excluded from write protection, e.g.:
● Activating/deactivating write protection
● Changing the access level (p0003)
● Saving parameters (p0971)
● Safely removing the memory card (p9400)
● Restoring the factory setting
● Importing settings from an external data backup, e.g. upload from a memory card to the
converter.
The individual parameters that are excluded from the write protection, can be found in the
List Manual in Chapter "Parameters for write protection and protection of know-how".
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
.
Write protection/know-how protection status
.00
Write protection active
Write protection (factory setting: 0)
0:
Deactivate write protection
1:
Activate write protection
Data backup and series commissioning
7.4 Write and know how protection
269