Installation
4.4 Connecting the inverter to the fieldbus
4.4.2.3

Configuring communication to the control

Configuring the communication with a SIMATIC S7 control
You have the following options, if the inverter is not included in the hardware library:
● Install the most up to date STARTER version
● Install the GSDML of the inverter using "Tools/Install GSDML file" in HW Config.
Further information is provided in the Fieldbus function manual.
Configuring the communication with a non-Siemens control
1. Import the device file (GSDML) of the inverter into the engineering tool for your control
system.
2. Configure the communication.
4.4.2.4

Installing GSDML

Procedure
To install the GSDML of the inverter into the configuring tool of your control system, proceed
as follows:
1. Save the GSDML to your PC .
– From the Internet: GSDML
– From your inverter:
2. Unzip the GSDML file to a folder on your computer.
3. Import the GSDML into the configuring tool of your control system.
You have now installed the GSDML.
86
Manuals for your converter (Page 335)
(http://support.automation.siemens.com/WW/view/en/22339653/133100).
Insert a memory card into the inverter.
Set p0804 = 12.
The inverter writes the GSDML as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG