Specifying The Setpoint Via The Fieldbus - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.3.2

Specifying the setpoint via the fieldbus

Interconnecting the fieldbus with the main setpoint
Figure 6-22
Most standard telegrams receive the speed setpoint as a second process data PZD2.
Table 6- 20
Parameter
p1070 = 2050[1]
p1075 = 2050[1]
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Fieldbus as setpoint source
Setting the fieldbus as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with process data PZD2 from the fieldbus.
Additional setpoint
Interconnect the additional setpoint with process data PZD2 from the fieldbus.
Advanced commissioning
6.3 Setpoints
205