Parameter p0301 must be set to 0
When commissioning using the manual input of motor data, it is important that p0301 is set
to 0.
If p0301 is not set to 0, then even if the motor ID function is selected at the completion of
the commissioning process, no motor ID will actually be performed. If the motor ID is not
performed it could leave the motor in an unpredictable state and that may adversely affect
the users application.
Therefore, it is essential that p0301 is checked to ensure it is actually set to 0.
Commissioning with the Intelligent Operator Panel (IOP)
When using the basic commissioning wizard on the IOP the user will presented with a
screen asking for the motor type (p0300) to be entered. Depending on the value that is input
into the IOP, there are two different branches to the commissioning wizard.
Action 1(using motor codes):
1. If 100 or 177 is entered, the user is then presented with the motor code screen (p0301).
2. Entered the relevant code for the motor.
3. The motor data is automatically assigned for the motor.
4. The basic commissioning wizard continues but does not ask for any further motor data to
be entered.
Action 2 (no motor codes):
1. If 1 is entered (Induction motor), the IOP will automatically set p0301 to 0.
2. The basic commissioning wizard continues and asks for the relevant motor data to be
entered during the commissioning process.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
CAUTION
Commissioning
5.3 Basic commissioning