Parameters
p2192
p2193 = 1
Monitoring, pump/fan
The monitoring functions for pumps and fans are similar. The blocking protection applies
equally to both applications.
For pumps, there is also a leakage monitoring function.
Principle of operation
Within speed thresholds 1 and 3, the inverter monitors the torque and the speed for pumps
and fans.
If the torque or the speed moves, for longer than the time set in p2192, in the ranges of
blockage, leakage or dry running protection/belt breakage, then the response defined in
p2181 is realized.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Description
Load monitoring delay time
Delay time for the message "Leave torque monitoring tolerance band"
Load monitoring configuration (factory setting: 1)
Table 6-39 Setting options for load monitoring (Page 233)

Advanced commissioning

6.7 Application-specific functions
235