Thermal motor model 2 for induction motors
The thermal motor model 2 for induction motors is a thermal 3-mass model, consisting of
stator core, stator winding and rotor.
Figure 6-38
Table 6- 32
Parameter Description
r0068
p0610
p0344
p0604
p0605
p0612
p0627
p0625
r0632
Further information is provided in the function charts 8016 and 8017 of the List Manual.
6.6.4

Overcurrent protection

The vector control ensures that the motor current remains within the set torque limits.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Thermal motor model 2 for induction motors
Thermal motor model 2 for induction motors
CO: Absolute actual current value
Motor overtemperature response (factory setting: 12)
0:
No response, alarm only, no reduction of I
1:
Messages, reduction of I
2:
Messages, no reduction of I
12:
Messages, no reduction of I
Motor weight (for thermal motor type) (factory setting: 0.0 kg)
Mot_temp_mod 2/KTY alarm threshold (factory setting: 130.0° C)
Motor temperature > p0604 ⇒ fault F07011.
Mot_temp_mod 1/2 threshold (factory setting: 145.0° C)
Motor temperature > p0605 ⇒ alarm A07012.
Mot_temp_mod activation
.01
1 signal: Activate motor temperature model 2 for induction
motors
.09
1 signal: Activate motor temperature model 2 expansions
The inverter sets bit 09 = 1 after commissioning. If you load
the parameter settings for firmware version ≤ V4.6 into the
inverter, bit 09 = 0 remains.
Motor overtemperature, stator winding (factory setting: 80 K)
Motor ambient temperature during commissioning (factory setting: 20° C)
Specification of the motor ambient temperature in °C at the instant of the motor data
identification.
Mot_temp_mod stator winding temperature [°C]
max
max
max
, temperature is saved
max

Advanced commissioning

6.6 Protection functions
After selecting an
induction motor
(p0300) or a listed
induction motor
(p0301) during the
commissioning,
the inverter sets
the parameters to
values appropriate
for the motor.
The parameters
are write-
protected for listed
motors
(p0301 ≥ 0).