Advanced commissioning
7.3 Setpoints
7.3.2

Analog input as setpoint source

Interconnecting an analog input
If you have selected a pre-assignment without a function of the analog input, then you must
interconnect the parameter of the main setpoint with an analog input.
Figure 7-10
Table 7- 5
Parameter
p1070 = 755[0]
p1075 = 755[0]
You must adapt the analog input to the connected signal, e.g. ± 10 V or 4 ... 20 mA. You will
find additional information in the section: Analog inputs (Page 122).
7.3.3

Specifying the setpoint via the fieldbus

Interconnecting the fieldbus with the main setpoint
Figure 7-11
Most standard telegrams receive the speed setpoint as a second process data PZD2.
Table 7- 6
Parameter
p1070 = 2050[1]
p1075 = 2050[1]
130
Example: Analog input 0 as setpoint source
Setting with analog input 0 as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with analog input 0
Additional setpoint
Interconnect the additional setpoint with analog input 0
Fieldbus as setpoint source
Setting the fieldbus as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with process data PZD2 from the fieldbus.
Additional setpoint
Interconnect the additional setpoint with process data PZD2 from the fieldbus.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB