Advanced Commissioning - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Advanced commissioning

6.7 Application-specific functions
Parameter
p3320 ...
p3329
r0039
p0040
r0041
r0042
p0043
230
Description
Flow characteristic
Factory setting of the flow characteristic
To set the characteristic, you require the following data from the machine manufactur-
er for each speed interpolation point:
The flow rate of the fluid-flow machine associated with the 5 selected converter
speeds
The power drawn at constant speed associated with the five flow rates corre-
sponds to the line frequency and mechanical throttling of the flow rate.
Energy display [kWh]
[0]
Energy balance
Energy usage since the last reset
[1]
Energy drawn since the last reset
[2]
Energy fed back since the last reset
Reset energy consumption display
A signal change 0 → 1 sets r0039[0...2] = 0, r0041 = 0 and r0042 = 0.
Energy consumption saved (kWh)
Energy saved referred to 100 operating hours.
For less than 100 operating hours, the inverter interpolates the energy saving to 100
operating hours.
CO: Process energy display [1 ≙ 1 Wh]
For display as process variable. Enable with p0043.
[0]
Energy balance
Energy consumption since the last reset.
[1]
Energy drawn since the last reset
[2]
Energy fed back since the last reset.
BI: Enable energy usage display
1 signal: Process energy display is active in r0042.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG

Advertisement

Table of Contents
loading

Table of Contents