Installation
4.2 System Installation
11. Connecting the power-through cables (Glanded variant)
12. Fitting the internal braking resistor
50
In the glanded variant the power-through connections use a
different methodology.
The Terminal Housing terminals L1, L2 and L3 require two
cables to be fitted to each terminal - this makes the maximum
cable cross-section 2.5 mm
connected to the terminals through a twin ferrule connector, as
shown in the callout in the figure on the right. The twin ferrules
are available from Phoenix Connector under article number:
3200836.
1. Connect the Input cables to the L1, L2 and L3 terminals of
the Terminal Housing.
2. Connect the Input earth cable to the first earthing post of
the Terminal Housing.
3. Connect the L1, L2 and L3 terminals of the Terminal
Housing to the output cable through the cable gland.
Note:
On the glanded variant no pre-cut cables are provided.
The internal braking resistor is an optional extra and is fitted
into the Terminal Housing.
1. Slide the internal braking resistor into place on the opposite
side to which the CPI will be fitted.
2. Fit the internal braking resistor securing bracket.
3. Secure the bracket in place using the two screws to a
tightening torque of 1.5 Nm.
4. Connect the internal braking resistor cables to the R2 and
R1 terminals of the Terminal Housing motor terminals.
Note:
The internal braking resistor can be fitted on the left or right
side of the Terminal Housing, but must always be fitted on the
opposite side of the Terminal Housing from Communications
and Power Interface (CPI).
. The input and output cables are
2
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG