Status word 3 (ZSW3)
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
6.2.4.3
Structure of the parameter channel
Structure of the parameter channel
The parameter channel consists of four words. 1. and 2nd word transfer the parameter
number and index as well as the type of job (read or write) The 3rd and 4th word contains
the parameter contents. The parameter contents can be 16-bit values (such as baud rate) or
32-bit values (e.g. CO parameters).
Bit 11 in the 1st word is reserved and is always assigned 0.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Significance
1 = DC braking active
1 = |n_act | > p1226
1 = |n_act | > p1080
1 = i_act ≧ p2170
1 = |n_act | > p2155
1 = |n_act | ≦ p2155
1 = |n_act | ≧ r1119
1 = DC link voltage ≦ p2172
1 = DC link voltage > p2172
1 = ramp-up or ramp-down complet-
ed
1 = technology controller output at
the lower limit
1 = technology controller output at
the upper limit
Not used
Not used
Not used
Not used
Description
--
Absolute current speed > stationary
state detection
Absolute actual speed > minimum
speed
Actual current ≥ current threshold
value
Absolute actual speed > speed
threshold value 2
Absolute actual speed < speed
threshold value 2
Speed setpoint reached
Actual DC link voltage ≦ threshold
value
Actual DC link voltage > threshold
value
Ramp-function generator is not
active.
Technology controller output ≦
p2292
Technology controller out-
put > p2291
Advanced commissioning
6.2 Inverter control
Signal intercon-
nection in the
inverter
p2051[3] = r0053
145