Advanced Commissioning - Siemens SINAMICS G110M Operating Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Table 6- 20
Parameter
p1035
p1036
p1040
p1047
p1048
r1050
p1070 =
1050
Table 6- 21
Parameter
p1030
p1037
p1038
p1039
p1041
p1043
p1044
For more information about the motorized potentiometer, refer to function diagram 3020 in
the List Manual.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Basic setup of motorized potentiometer
Description
Motorized potentiometer setpoint higher
Motorized potentiometer setpoint lower
MOP start value (factory setting: 0 rpm)
Defines the start value [rpm] that is effective when the motor is switched on.
MOP ramp-up time (factory setting: 10 s)
MOP ramp-down time (factory setting: 10 s)
Motorized potentiometer setpoint after the ramp-function generator
Main setpoint
Extended setup of motorized potentiometer
Description
MOP configuration (factory setting: 00110 bin)
.00
Storage active
= 0: After the motor has been switched on, the setpoint = p1040
= 1: After the motor has switched off, the inverter saves the setpoint. After the
motor has switched on, the setpoint = the stored value
.01
Automatic mode, ramp-function generator active (1-signal via BI: p1041)
= 0: Ramp-up/ramp-down time = 0
= 1: With ramp-function generator
In manual mode (p1041 = 0), the ramp-function generator is always active.
.02
Initial rounding active
1: With initial rounding. Using the initial rounding function it is possible to enter
very small setpoint changes
.03
Storage in NVRAM active
1: If bit 00 = 1, the setpoint is retained during a power failure
.04
Ramp-function generator always active
1: The inverter also calculates the ramp-function generator when the motor is
switched off
MOP maximum speed (factory setting: 0 rpm)
Automatically pre-assigned when commissioning
MOP minimum speed (factory setting: 0 rpm)
Automatically pre-assigned when commissioning
Motorized potentiometer, inversion (factory setting: 0)
Signal source for inverting the minimum speed / velocity or maximum speed / velocity
Motorized potentiometer, manual/automatic (factory setting: 0)
Signal source for switchover from manual to automatic
Motorized potentiometer, accept setting value (factory setting: 0)
Signal source for accepting the setting value. The motorized potentiometer accepts
the setting value p1044 on signal change p1043 = 0 → 1.
MOP setting value (factory setting: 0)
Signal source for the setting value.

Advanced commissioning

Interconnect these commands with sig-
nals of your choice.
6.3 Setpoints
169