Advanced commissioning

6.2 Inverter control
AS-i.P3
Fixed speeds - Dual Slave
Table 6- 14
AS-i.DO2
Alarm and fault messages
Table 6- 15
RP3 RP2 RP1 RP0 AS-i.P0 = 0 -> alarm messages
0
0
0
0
0
0
0
0
1
1
1
1
1
158
AS-i.P2
AS-i.P1
0
0
0
0
0
0
Fixed speeds via the motor control bits and response in the inverter
AS-i.DO1
AS-i.DO0
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
Alarm and fault messages via RP0 ... RP3 from the inverter to the AS-i master
0
0
0
No alarm
0
0
1
not used
0
1
0
not used
0
1
1
No load (A07929)
1
0
0
Overtemperature (A07400,
A07404. A30502)
1
0
1
Overvoltage (A07400, A07404,
A30502)
1
1
0
not used
1
1
1
Undervoltage (A30041, A07402,
A07403, A30016)
0
0
0
I
t overload (A08705)
2
0
0
1
not used
0
1
1
not used
1
0
0
not used
1
0
1
Motor phase loss
AS-i.P0
Scaling factor
1
0.07
0
0.05
Response in the inverter
0
OFF1
1
On + fixed speed 1 (factory setting: 1500 rpm)
0
On + fixed speed 2 (factory setting: -1500 rpm)
1
On + fixed speed 3 (factory setting: 300 rpm)
0
On + fixed speed 4 (factory setting: 450 rpm)
1
On + fixed speed 5 (factory setting: 600 rpm)
0
On + fixed speed 6 (factory setting: 750 rpm)
1
Acknowledge fault or OFF2
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Frequency (Hz)
3.5
2.5
AS-i.P0 = 1 -> faults
No fault
Overtemperature, F00004, F00006
not used
not used
I
t overload (F30005, F07936)
2
Equipment malfunction (F30009,
F01000, F01001, F01002, F01005,
F01015, F01018, F01029, F01000-
F01300)
not used
Motor-PTC sensor malfunction
(F07011, F07016)
Overvoltage (F30002, F30011)
not used
Undervoltage (F00003, F30040,
F07802)
Short-circuit at the output (F30001,
F30017, F30021, F07801, F07808,
F07900, F30017, F07807)
Motor phase loss (F30015, F07902)