The inverter shifts the values previously saved in the fault history by eight indexes. Faults,
which were saved in indexes 56 ... 63 before the acknowledgement, are deleted.
Deleting the fault history
If you wish to delete all faults from the fault history, set parameter p0952 to zero.
Parameters of the fault buffer and the fault history
Parameter
r0945
r0948
r0949
p0952
r2109
r2130
r2131
r2133
r2136
Extended settings for faults
Parameter
You can modify the motor fault response for up to 20 different fault codes:
p2100
p2101
You can modify the acknowledgement type for up to 20 different fault codes:
p2126
p2127
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Description
Fault code
Displays the numbers of faults that have occurred
Fault time received in milliseconds
Displays the time in milliseconds when the fault occurred
Fault value
Displays additional information about the fault
Fault cases, counter
Number of fault cases that have occurred since the last acknowledgement.
The fault buffer is deleted with p0952 = 0.
Fault time removed in milliseconds
Displays the time in milliseconds when the fault occurred
Fault time received in days
Displays the time in days when the fault occurred
Actual fault code
Displays the code of the oldest fault that is still active
Fault value for float values
Displays additional information about the fault that occurred for float values
Fault time removed in days
Displays the time in days when the fault was removed
Description
Setting the fault number for fault response
Selecting the faults for which the fault response should be changed
Setting, fault response
Setting the fault response for the selected fault
Setting the fault number for the acknowledgement mode
Selection of the faults for which the acknowledgement type should be changed
Setting, acknowledgement mode
Setting the acknowledgement type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgement after removing the fault cause
Alarms, faults and system messages
9.3 Faults