IPMEDPRO (IP Media Processor Circuit Pack)
Table 10-336. TEST #52 Control Channel Looparound Test — Continued
Error
Code
FAIL
PASS
0
NO
BOARD
SAKI Sanity Test (#53)
This is a destructive test.
This test is only run as a part of a reset board procedure. For the Media
Processor, it is necessary to use the change ip-interfaces form to disable the
Media Processor IP interface before performing this reset board procedure. Other
common circuit packs can be reset with the reset board UUCSS command which
also executes this test.
A reset of this circuit pack will take about 3 1/2 minutes.
555-233-123
Test
Description/Recommendation
Result
The circuit pack failed to return the circuit pack code or
vintage.
1. Retry the command a maximum of 5 times.
2. If the problem continues, replace the circuit pack.
3. Retry the command a maximum of 5 times.
Communication with this circuit pack is successful.
The test could not relate the internal ID to the port (no board).
This could be due to incorrect translations, no board is
inserted, an incorrect board is inserted, or an insane board is
inserted.
1. Ensure that the board translations are correct.
Administer the MedPro interface if it is not already
administered.
2. If the board was already administered correctly,
check the error log to determine whether the board is
hyperactive. If this is the case, the board is shut
down. Reseating the board re-initializes the board.
3. If the board was found to be correctly inserted in
step 1, then issue the busyout board UUCSS
command.
4. Issue the reset board UUCSS command.
5. Issue the release board UUCSS command.
6. Issue the test board UUCSS long command.
This should re-establish the linkage between the internal ID
and the port.
Continued on next page
Issue 4 May 2002
10-925