Connecting and commissioning

9.1

Overview of safety and commissioning

Dangerous electrical voltage!
When operating electrical devices, certain parts of these devices are necessarily under
dangerous voltage. Failure to observe the operating instructions can therefore result in serious
injury or material damage.
Observe the operating instructions.
Risk of injury during commissioning
• The door movements cannot always be externally controlled while the controller is being
• Increased forces and energies can occur during the learn run. The force during the learn run
An authorized person must therefore be posted near the door to ensure that no one else can
enter the vicinity of the door during commissioning.
Note
The motor temperature must not lie below 0 °C during the learn run, as otherwise the mass to
be moved will be incorrectly determined, and the opening and closing speed may lie in an
impermissible range.
Working on the door drive
Risk of injury due to dangerous electrical voltages and moving mechanical parts.
Disconnect the door drive by unplugging the power plug from the power supply before you
start work on the door drive.
AT40 and ATD400V for elevators
System Manual, 06/2022, A5E42192709-AH
WARNING
WARNING
commissioned (in particular during the automatic determination of parameters). The light
barrier is not active during the learn run.
can be configured. The default values for closing direction Motor M2 are: 120 N; M3, M4,
M5: 230 N. Opening direction motor M2: 120 N; M3: 300 N; M4, M5: 360N.
WARNING
9
157