3.2 Electrical Installation

3.2.1 Electrical Installation in General

All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors are required. 75 °C (167 °F) is recommended.
Power [kW(HP)]
Frame
IP class
3x200-240 V
H1
IP20
0.25–1.5
(0.33-2)
H2
IP20
2.2 (3)
H3
IP20
3.7 (5)
H4
IP20
5.5–7.5 (7.5-10)
H5
IP20
11 (15)
H6
IP20
15–18.5 (20–25)
H7
IP20
22–30 (30–40)
H7
IP20
H8
IP20
37–45 (50–60)
Table 3.5 Tightening Torques for Enclosure H1-H8, 3x200-240 V & 3x380-480 V
Power [kW(HP)]
Frame
IP class
3x380-480 V
I2
IP54
0.75–4.0 (1–5)
I3
IP54
5.5–7.5 (7.5-10)
I4
IP54
11–18.5 (15–25)
I6
IP54
22–37 (30–50)
I7
IP54
45–55 (60–70)
I8
IP54
75–90 (100–125)
Table 3.6 Tightening Torques for Enclosure I1–I8
Power [kW]
Frame
IP class
3x525-600 V
H9
IP20
2.2–7.5 (3–10)
H10
IP20
11–15 (15-20)
H6
IP20
18.5–30 (25-40)
H7
IP20
37–55 (50–70)
H8
IP20
75–90 (100–125)
Table 3.7 Tightening Torques for Enclosure H6-H10, 3x525-600 V
≤ 95 mm
2
1) Cable dimensions
2) Cable dimensions >95 mm
2
MG18A602
Quick Guide
3x380-480 V
Mains
0.37–1.5 (0.5–2)
0.8 (7)
2.2–4.0 (3–5)
0.8 (7)
5.5–7.5 (7.5-10)
0.8 (7)
11–15 (15-20)
1.2 (11)
18.5–22 (25-30)
1.2 (11)
30–45 (40–60)
4.5 (40)
55 (70)
10 (89)
75 (100)
14 (124)
90 (125)
2)
24 (212)
24 (212)
Mains
Motor
0.8 (7)
0.8 (7)
0.8 (7)
0.8 (7)
1.4 (12)
0.8 (7)
4.5 (40)
4.5 (40)
10 (89)
10 (89)
14 (124)/24
14 (124)/24
(212)
1)
(212)
1)
Mains
Motor
1.8 (16)
1.8 (16)
1.8 (16)
1.8 (16)
4.5 (40)
4.5 (40)
10 (89)
10 (89)
14 (124)/24
14 (124)/24
1)
1)
(212)
(212)
Danfoss A/S © 08/2014 All rights reserved.
Torque [Nm(in-lb]
Motor
DC
Control
connection
terminals
0.8 (7)
0.8 (7)
0.5 (4)
0.8 (7)
0.8 (7)
0.5 (4)
0.8 (7)
0.8 (7)
0.5 (4)
1.2 (11)
1.2 (11)
0.5 (4)
1.2 (11)
1.2 (11)
0.5 (4)
4.5 (40)
0.5 (4)
10 (89)
0.5 (4)
14 (124)
0.5 (4)
2)
0.5 (4)
Torque [Nm(in-lb]
DC
Control
connection
terminals
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.5 (4)
0.5 (4)
0.5 (4)
Torque [Nm(in-lb)]
DC
Control
connection
terminals
not
0.5 (4)
recommended
not
0.5 (4)
recommended
0.5 (4)
0.5 (4)
0.5 (4)
Ground
Relay
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
Ground
Relay
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
3 (27)
0.6 (5)
3 (27)
0.6 (5)
3 (27)
0.6 (5)
Ground
Relay
3 (27)
0.6 (5)
3 (27)
0.6 (5)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
9
3
3