12. Factory Setting Recovering and Middleware
Updating
This chapter will introduce the settings by hardware Rotary Switch, including "Factory
Setting Recovering" and "Middleware Updating" that supported since Version 1.0.0.3.

12.1. Recovering to Factory Setting (Rotary Switch: 8)

Turn the Rotary Switch of UA-5200 series to "8" can recover to the factory setting. Before
that, first to connect the UA controller via a network cable to a PC or a Switch.
The steps:
1.
After network connection, power off the UA-5200 hardware, and turn the Rotary
Switch to "8".
2.
Reboot the UA-5200 and wait a long buzzer sound that means of doing the recovering.
3.
Wait about 3 minutes until
"0". Note: If the buzzer makes
properly. Please check the network cable again.
4.
Reboot the UA-5200 again, and the system will recover to the factory settings.
Network
OS
Account
Web UI
Account
2
long buzzer sounds, and then turn the Rotary Switch to
4
short beeps, it means the network is not connected
Factory Default Settings of UA-5200
IP
192.168.255.1
Netmask
255.255.0.0
Gateway
192.168.1.1
Username
root
Password
icpdas
Username
root
Password
root
UA-5200 Series User Manual V4.3
Assign UA-5200 a new IP
setting according to your
case.
After login, change your
password ASAP. (Refer to
Section
210
5.4)
ICP DAS

Advertisement