[Module Content Setting] page can set up the module and the Modbus address
mapping table:
Module Content Setting
No.
Module Name
Slave ID
Timeout
Modbus Mapping Table Setting
Data Model
Start Address
Data Number
Type
Create Tables
The module number in the module list (Not editable here)
Give a name, e.g. model number or name. Default: Name.
Set the module Slave ID of the UA-5200. (Range: 1 ~ 247)
Set the timeout value for the module. Default: 500 ms
System provides 4 Modbus data models
"01" ~ "04" for mapping to address of
DO, DI, AO and AI. (ex. 01: DO
channels, 02: DI, 03: AO, 04: AI)
The start address of the Modbus command.
UA controller is start from 0, even if some modules are start from 1,
here it needs to set follow the UA series to start from 0.
The number of the Modbus address. Need to give enough number
for the DO, DI, AO, AI channels of the module. Default: 1.
This item only when the data model is 03 or 04. Choose the
suitable data type: 16-bit Short, 16-bit Unsigned Short, 32-bit Long,
32-bit Unsigned Long, 32-bit Float, 64-bit Double.
Click [Add] button, it will add a table in the Modbus mapping table.