ICP DAS USA UA-5200 Series User Manual page 149

Iiot communication server
Hide thumbs Also See for UA-5200 Series:
Table of Contents

Advertisement

Click [Edit] button to enter the "Module Content Setting" page.
Module Content Setting
No.
Module Name
Slave ID
Timeout
Modbus Mapping Table Setting
Data Model
Start Address
Data Number
Type
Create Tables
The module number in the module list (Not editable here)
Give a name, e.g. model number or name. Default: Name.
Set the module Slave ID of the UA-5200. (Range: 1 ~ 247)
Set the timeout value for the module. Default: 500 ms
System provides 4 Modbus data models
"01" ~ "04" for mapping to address of
DO, DI, AO and AI. (ex. 01: DO
channels, 02: DI, 03: AO, 04: AI)
The start address of the Modbus command.
controller is start from 0, even if some modules are start from 1, here it
needs to set follow the UA series to start from 0.
The number of the Modbus address. Need to give enough number for
the DO, DI, AO, AI channels of the module. Default: 1.
This item only when the data model is 03 or 04. Choose the suitable
data type: 16-bit Short, 16-bit Unsigned Short, 32-bit Long, 32-bit
Unsigned Long, 32-bit Float, 64-bit Double.
Click [Add] button, it will add a table in the Modbus mapping table.
UA-5200 Series User Manual V4.3
149
Note:
the address of UA
ICP DAS

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ua-5231m-3gwaUa-5231m-4geUa-5231Ua-5231m-4gcUa-5231m

Table of Contents